Search

Searching. Please wait…

Detection of ferroresonance occurrence in inductive voltage transformers through vibration analysis

Abstract: Steady state ferroresonances in isolated neutral electrical systems result in sustained abnormal system oscillations, which can damage inductive voltage transformers (IVTs) and other system elements. During this phenomenon, the IVT becomes saturated; consequently, the dimensions of the ferromagnetic material of the IVT change owing to magnetostriction. Because of this inherently nonlinear behaviour, the natural vibration modes of the IVT are excited. The aim of this study is to take advantage of these anomalous vibration modes to reveal the occurrence of ferroresonance in IVTs. The methodology for ferroresonance detection in IVTs through vibration analysis is described and demonstrated experimentally.

 Authorship: Arroyo A., Martinez R., Manana M., Pigazo A., Minguez R.,

 Fuente: International Journal of Electrical Power and Energy Systems, 2019, 106, 294-300

 Publisher: Elsevier

 Publication date: 01/03/2019

 No. of pages: 7

 Publication type: Article

 DOI: 10.1016/j.ijepes.2018.10.011

 ISSN: 0142-0615

 Spanish project: RTC-2015-4176-3

 Publication Url: https://doi.org/10.1016/j.ijepes.2018.10.011