Abstract: In this paper, an experimental and numerical research was conducted to study the aging effect on the cooling performance of a natural ester habitually used in power transformers. A monitored experimental platform has been used to observe the temperature increases with the aging of the ester. Three samples with three aging levels (fresh oil, aged oil and aged oil with paper) were tested at three load levels, C=0.72, C=1 and C=1.3 (9 tests). The two aged samples (6 liters each) were aged in an accelerated way within an oven: 1 week at 150°C. Also, some physicochemical properties of the insulation system were determined. In the case of the liquid, viscosity, moisture, acidity, dissipation factor (90 °C) were measured. The degree of polymerization and the moisture were measured in paper samples. A 2D numerical model has been developed with COMSOL Multiphysics to replicate the thermal-hydraulic behavior of the samples in the platform. That is, the idea is to determine the temperature and velocity distributions of the different samples in order to analyze their differences and to compare their cooling capacity. At first sight, the aging affects negatively to the cooling capacity of the new alternative liquid based on natural esters.
Autoría: Ortiz A., Delgado F., Ortiz F., Fernández I., Santisteban A.,
Fuente: Applied Thermal Engineering, 2018, 144, 797-803
Editorial: Elsevier Ltd
Fecha de publicación: 05/11/2018
Nº de páginas: 11
Tipo de publicación: Artículo de Revista
DOI: 10.1016/j.applthermaleng.2018.08.049
ISSN: 1359-4311,1873-5606
Proyecto español: DPI2015-71219-C2-1-R
Url de la publicación: https://doi.org/10.1016/j.applthermaleng.2018.08.049
SCOPUS
Citas
Google Scholar
Métricas
Repositorio UCrea Leer publicación
ALFREDO ORTIZ FERNANDEZ
FERNANDO DELGADO SAN ROMAN
FELIX ORTIZ FERNANDEZ
INMACULADA FERNANDEZ DIEGO
AGUSTIN SANTISTEBAN DIAZ
Volver