Abstract: The thermal behavior of an industrial Low Voltage non-segregated three-phase busduct was analyzed by means of the comparison of a 3D numerical model with experimental results. This model has been carried out using COMSOL Multiphysics, software based on finite element method. The numerical model replicates the short-circuit test, using the same geometry configuration and the boundary conditions of the laboratory in which this assay was carried out. The standard IEC 61439 was applied, both in test and model, in order to obtain the steady state temperatures in several parts of the busbar system. As a result of the data comparison can be concluded that the experimental test was replicated by the numerical model with sufficient accuracy. The temperature differences between simulation results and those of the heating tests were in a narrow range. On the other hand, a sensitivity analysis was carried out with the intention to study the influence of sensors positioning on the temperature measurement in the laboratory test, thus concluding no high precision was needed in the location of the temperature meters. As a final conclusion of this study, it is needed to point out that the numerical model has the enough exactness to be used in the first steps of the busbar design.
Autoría: Delgado F., Renedo C., Ortiz A., Fernández I., Santisteban A.,
Fuente: Applied Thermal Engineering, 2017, 110, 1643-1652
Editorial: Elsevier Ltd
Fecha de publicación: 05/01/2017
Nº de páginas: 19
Tipo de publicación: Artículo de Revista
DOI: 10.1016/j.applthermaleng.2016.09.002
ISSN: 1359-4311,1873-5606
Proyecto español: DPI2013-43897-P
Url de la publicación: https://doi.org/10.1016/j.applthermaleng.2016.09.002
SCOPUS
Citas
Google Scholar
Métricas
Repositorio UCrea Leer publicación
FERNANDO DELGADO SAN ROMAN
CARLOS JAVIER RENEDO ESTEBANEZ
ALFREDO ORTIZ FERNANDEZ
INMACULADA FERNANDEZ DIEGO
AGUSTIN SANTISTEBAN DIAZ
Volver